Tender detail
40 kVA Three-Phase UPS (Uninterruptible Power Supply)
Summary
The contract concerns the supply of a 40 kVA three-phase UPS system for DR Congo. The bid should include a 40 kVA Online Double Conversion UPS with a maximum load capacity of about 21.5 kW (design margin to about 32 kW), PF ≥ 0.9, minimum autonomy of 30 minutes, Lithium batteries, integrated maintenance bypass, Automatic Transfer Switch (ATS), Surge Protection Devices, grounding and earthing, 400 V AC input and 400/230 V AC output, SNMP/web-based remote monitoring, scalable architecture, and compatibility with the existing generator GE.PK.110100.PRO+011. Prices must be in EUR net.
More tender information after sign-in